National Fire Protection Association (NFPA)'s Blog, page 12

September 29, 2022

Electrical space: the final frontier where electrical inspectors voyage to explore two of the many requirements of section 110.26(A)

Electrical space: the final frontier. “These are the voyages of the electrical inspector.” This plays on a quote from one of my favorite Star Trek movies. Space, especially electrical equipment space in buildings, can seem like it is a final frontier because it is getting harder to come by. Or is it? Prior to the COVID outbreak, buildings were being built to house hundreds, even thousands of employees, so space for electrical and mechanical rooms was at a premium and in tight quarters. Office space, especially when being rented by the square foot, was made a higher priority. With the way that many of us work shifting due to the pandemic, designs of buildings are likely to also start shifting to accommodate the move to a more remote workforce, which occupies less space within buildings. This may cause office spaces to be consolidated, therefore giving more room for electrical and mechanical rooms. Consolidation of space for offices may be occurring, but the change in how we work appears aimed more at having open spaces being converted to conference rooms for team meetings. But no matter what is occurring in the space designated for offices or meeting rooms, the one area that cannot be compromised is the spaces about electrical equipment. There are two types of spaces around electrical equipment mentioned in the 2023 National Electrical Code® (NEC®): working space and dedicated equipment space. Each one has quite different requirements, but all aid in the safety of the worker and longevity of the installation.Working space within the NEC, in general, is comprised of three parts: Depth of Working Space - found in section 110.26(A)(1). This measurement factors in nominal voltage to ground and if there are grounded parts or exposed live parts across from the equipment. Measurements are taken from live exposed parts or from enclosure if live parts are enclosed, out the front until the minimum distance found in Table 110.26(A)(1) is met. Width of Working Space –in section 110.26(A)(2). This dimension is derived by measuring the width across the front of the equipment. This can be taken from center (15 inches in middle of equipment), from left side of equipment or from right side. No matter the voltage or amperage the width will never be less than 30 inches. Height of working Space – addressed in 110.26(A)(3). This is measured from grade, floor, or platform to a height of 6.5 feet and is the width of the equipment or minimally 30 inches.All these spaces combine to form a box, if you will, that is for the qualified worker to occupy when servicing or working on the equipment. This is intended to provide room to move, which is necessary to keep them from bumping into something and possibly getting shocked or causing an arc flash. This area also allows easy access to equipment should a breaker or disconnect need to be shut off quickly. Working space is not to be used for storage according to 110.26(B). In all my years as an inspector I can’t tell you how many times I have had to write that violation during the electrical inspections. These mostly occurred on remodels where circuits and wiring were added to the existing electrical systems. I would politely remind the building owner/occupant that working space was required to help keep the electrical worker safe from exposure to electrical hazards that may be present. New to the 2023 NEC in section 110.26(A)(6) is the requirement that the grade, floor or platform in the working space be clear and as level or flat as practical for the entire required depth and width.The dedicated equipment space in 110.26(E) is just what you would think it would be; space dedicated solely for the installation of electrical equipment. Indoor dedicated electrical space is found in 110.26(E)(1)(a), which electrical inspectors often refer to as the “thumb print” of the equipment plus six feet above the top of the equipment. For example, a panelboard 20-inches wide x 6-inches deep mounted to the surface of the wall at seven feet to the top would have dedicate electrical space extending up to 13 ft above the finished floor. So the overall dedicated space is 20-inches wide x 6-inches deep up to 13 ft. In general, only electrical items are allowed within that space, which might include: raceways (and associated fittings) wireways junction boxesThis list is not all inclusive, but an idea of what may be seen within the vicinity of electrical equipment. One exception to the dedicated space requirement is made for suspended ceilings with removable panels. With design limitations imposed on room size, there may be the occasional foreign system intruding into the dedicated electrical space required by section 110.26(E)(1)(a), typically becoming a violation. So, if the system was installed in accordance with 110.26(E)(1)(b), which addresses foreign systems over the dedicated electrical space, there would not be a problem. Remember our example, the top of the dedicated electrical space was 13 feet above finished floor, so the foreign system would need to be higher than 13 feet. If a foreign system is subject to condensation or leaks, the electrical equipment would require protection from such occurrences, which may also mean the system needs to be higher since the method of protection is not allowed within the dedicated electrical space. This space was put into the code to ensure adequate access to the electrical system for the installation of associated parts and to protect the electrical installation from other systems foreign to the electrical system.Electrical space: the final frontier where the voyages of the electrical inspector have explored two of the many requirements of section 110.26(A). Find more information for electrical inspectors by visiting nfpa.org/electricalinspection. You can explore the 2023 NEC by purchasing a printed copy or have NFPA LiNK® beamed to your computer.
 •  0 comments  •  flag
Share on Twitter
Published on September 29, 2022 17:00

Electrical Space: The Final Frontier

Electrical space: the final frontier. “These are the voyages of the electrical inspector.” This plays on a quote from one of my favorite Star Trek movies. Space, especially electrical equipment space in buildings, can seem like it is a final frontier because it is getting harder to come by. Or is it? Prior to the COVID outbreak, buildings were being built to house hundreds, even thousands of employees, so space for electrical and mechanical rooms was at a premium and in tight quarters. Office space, especially when being rented by the square foot, was made a higher priority. With the way that many of us work shifting due to the pandemic, designs of buildings are likely to also start shifting to accommodate the move to a more remote workforce, which occupies less space within buildings. This may cause office spaces to be consolidated, therefore giving more room for electrical and mechanical rooms. Consolidation of space for offices may be occurring, but the change in how we work appears aimed more at having open spaces being converted to conference rooms for team meetings. But no matter what is occurring in the space designated for offices or meeting rooms, the one area that cannot be compromised is the spaces about electrical equipment. There are two types of spaces around electrical equipment mentioned in the 2023 National Electrical Code® (NEC®): working space and dedicated equipment space. Each one has quite different requirements, but all aid in the safety of the worker and longevity of the installation.Working space within the NEC, in general, is comprised of three parts: Depth of Working Space - found in section 110.26(A)(1). This measurement factors in nominal voltage to ground and if there are grounded parts or exposed live parts across from the equipment. Measurements are taken from live exposed parts or from enclosure if live parts are enclosed, out the front until the minimum distance found in Table 110.26(A)(1) is met. Width of Working Space –in section 110.26(A)(2). This dimension is derived by measuring the width across the front of the equipment. This can be taken from center (15 inches in middle of equipment), from left side of equipment or from right side. No matter the voltage or amperage the width will never be less than 30 inches. Height of working Space – addressed in 110.26(A)(3). This is measured from grade, floor, or platform to a height of 6.5 feet and is the width of the equipment or minimally 30 inches.All these spaces combine to form a box, if you will, that is for the qualified worker to occupy when servicing or working on the equipment. This is intended to provide room to move, which is necessary to keep them from bumping into something and possibly getting shocked or causing an arc flash. This area also allows easy access to equipment should a breaker or disconnect need to be shut off quickly. Working space is not to be used for storage according to 110.26(B). In all my years as an inspector I can’t tell you how many times I have had to write that violation during the electrical inspections. These mostly occurred on remodels where circuits and wiring were added to the existing electrical systems. I would politely remind the building owner/occupant that working space was required to help keep the electrical worker safe from exposure to electrical hazards that may be present. New to the 2023 NEC in section 110.26(A)(6) is the requirement that the grade, floor or platform in the working space be clear and as level or flat as practical for the entire required depth and width.The dedicated equipment space in 110.26(E) is just what you would think it would be; space dedicated solely for the installation of electrical equipment. Indoor dedicated electrical space is found in 110.26(E)(1)(a), which electrical inspectors often refer to as the “thumb print” of the equipment plus six feet above the top of the equipment. For example, a panelboard 20-inches wide x 6-inches deep mounted to the surface of the wall at seven feet to the top would have dedicate electrical space extending up to 13 ft above the finished floor. So the overall dedicated space is 20-inches wide x 6-inches deep up to 13 ft. In general, only electrical items are allowed within that space, which might include: raceways (and associated fittings) wireways junction boxesThis list is not all inclusive, but an idea of what may be seen within the vicinity of electrical equipment. One exception to the dedicated space requirement is made for suspended ceilings with removable panels. With design limitations imposed on room size, there may be the occasional foreign system intruding into the dedicated electrical space required by section 110.26(E)(1)(a), typically becoming a violation. So, if the system was installed in accordance with 110.26(E)(1)(b), which addresses foreign systems over the dedicated electrical space, there would not be a problem. Remember our example, the top of the dedicated electrical space was 13 feet above finished floor, so the foreign system would need to be higher than 13 feet. If a foreign system is subject to condensation or leaks, the electrical equipment would require protection from such occurrences, which may also mean the system needs to be higher since the method of protection is not allowed within the dedicated electrical space. This space was put into the code to ensure adequate access to the electrical system for the installation of associated parts and to protect the electrical installation from other systems foreign to the electrical system.Electrical space: the final frontier where the voyages of the electrical inspector have explored two of the many requirements of section 110.26(A). Find more information for electrical inspectors by visiting nfpa.org/electricalinspection. You can explore the 2023 NEC by purchasing a printed copy or have NFPA LiNK® beamed to your computer.
 •  0 comments  •  flag
Share on Twitter
Published on September 29, 2022 17:00

September 25, 2022

New RFP Open, Due October 14, for FPRF Project: Smoke Detector Spacing on High Ceilings – Phase II

The Fire Protection Research Foundation is seeking proposals to identify a project contractor for a new project aiming to develop guidance for the installation of smoke detectors on smooth ceilings over 10 ft (3 m) in height that can be used as the technical basis for any changes to applicable codes and standards.As background, there has been confusion in design and code enforcement communities on what to do when smoke detectors are installed on ceilings higher than 10 ft (3 m). While NFPA 72®, National Fire Alarm and Signaling Code®, contains a table that allows for reduction of spacing for heat detection, it does not address spacing considerations for smoke detection based on ceiling heights.A previous literature review and gap analysis study on smoke detectors in high ceiling spaces was published by the Research Foundation in 2017. The outcomes of this study indicated that there was limited context and significant knowledge gaps that preclude the formulation of scientifically justified prescriptive requirements regarding smoke detector spacing relative to ceiling height. This study outlined a path forward to better characterize smoke detector spacing in high ceilings, such as by establishing a performance metric for smoke detectors that can be applied to high ceilings.Since the fire protection industry still needs additional information on the impact of ceiling height and detector spacing on smoke detection performance, the Research Foundation has initiated a project to address this issue through a literature review, data collection, modeling, and validation testing effort. The overarching objective of this study is to develop prescriptive guidance on the spacing of smoke detectors on ceiling heights greater than 10 ft (3 m) and specify the height at which performance-based strategies should be leveraged. The open RFP seeking a contractor for the “Smoke Detector Spacing on High Ceilings – Phase II” project is available here or on the Foundation’s website. Instructions on how to respond are included in the RFP.Please submit your proposals to Victoria Hutchison by October 14, 2022, at 5 p.m. ET.
 •  0 comments  •  flag
Share on Twitter
Published on September 25, 2022 17:00

September 22, 2022

“Research: the distance between an idea and its realization” – David Sarnoff, Pioneer of American radio and television

This was the quote used by Rodger Reiswig of JCI last week in his keynote to kick off the Detection portion of the 18th Annual SupDet program hosted by the Fire Protection Research Foundation in Atlanta, GA. The Fire Protection Research Foundation hosts a technical conference held annually called “SupDet”, which focuses on specific research applications in the Suppression (hence “Sup”), and Detection (“Det”) industries.Mr. Reiswig continued to highlight the impact research has made in the in the fire protection industry. This year, the detection portion of the conference focused on research in several critical areas including detection and signaling for First Responders, Residential Spaces, Wildfire and Smart Technology Systems.Maria Marks, of Siemens, and Jason Webb, Potter Electric Signals, presented on Fire Prevention and Code Compliance in the Age of Information and Automation. As the Internet of Things and the Cloud continue to evolve, the Maria and Jason discussed the impact to life safety systems. Their passion was evident as they described the methods in which systems are being monitored, inspected, and tested, via unmanned equipment such as drones, and robots, as well as handheld devices such as tablets and smartphones. Maria and Jason further explained the benefits and concerns associated with such tasks and even went into how specific NFPA codes and standards (provided below) address automated inspection, testing, and maintenance. NFPA 13, Standard for the Installation of Sprinkler Systems NFPA 14, Standard for the Installation for Standpipe and Hose Systems NFPA 20, Standard for the Installation of Stationary Fire Pumps for Fire Protection NFPA 25, Standard for the Inspection, Testing, and Maintenance of Water-Based Fire Protection Systems NFPA 72, National Fire Alarm and Signaling Code ® NFPA 915, Standard for Remote Inspections (proposed standard)If you missed SupDet, the slides from the presentations will be posted shortly on the SupDet website!
 •  0 comments  •  flag
Share on Twitter
Published on September 22, 2022 17:00

September 15, 2022

Research Foundation 40th anniversary webinar series recordings now available

The Fire Protection Research Foundation (FPRF), research affiliate of the National Fire Protection Association (NFPA®), conducted a two-day webinar series on August 24 and 25, 2022, celebrating its 40th anniversary this year. The webinar series covered research topic areas and themes that are aligned with research priorities of FPRF and the fire and life safety industry. This webinar series consisted of presentations by subject matter experts addressing the following themes: Day 1 program: Webinar recording Reduce Residential Fire Losses Fire Safety in the US since 1980 Cooking fires Impact of Medications on Older Adult Fall and Fire Risk Strategies for Community Resilience Wildland & Wildland Urban Interface Fires CAREDEX: Disaster Resilience in Aging Communities via a Secure Data Exchange Global Community Resilience Data Collection and Data Analytics to Inform Policy Global Fire data standardization Insurance Data – openIDL CRAIG 1300TM National Firefighter Cancer Registry Day 2 program: Webinar recording Hazards of New Materials and Systems Fire Safety Challenges of Green Buildings Energy Storage Systems Hazards of Modern Vehicles in Parking Structures Increase Effectiveness and Reliability of Safety Systems Impact of Research on NFPA 13 Impact of Research on NFPA 72 Effectiveness of fluorine free firefighting foams Fire Fighting Safety & Effectiveness Fire Service Contamination control & PPE Cleaning validation Firefighting foams: fire service roadmap Firefighter immersive learning training  If you missed attending this webinar series, the presentation recordings are now available to view on demand at www.nfpa.org/webinars. To learn more about the Research Foundation and our work over the last four decades, please visit: www.nfpa.org/fprf40.
 •  0 comments  •  flag
Share on Twitter
Published on September 15, 2022 17:00

A Closer Look at Some Assembly Occupancy Requirements

The fire at a Thai nightclub in early August 2022 was all too familiar. It started during a live music performance killing 20 people and injuring 25. Many of the details emerging are eerily similar to The Station nightclub fire which claimed the lives of 100 people and injured 230 more in February of 2003. In both instances, flammable interior finish and blocked exits were believed to have played a role in the fast-spreading fires and high number of fatalities. The 2003 tragedy led to a number of changes to NFPA 101, Life Safety Code, while also reiterating the importance of interior finish and means of egress requirements for assembly occupancies.Interior finishes are the interior surfaces of a building that are generally secured in place like wall and ceiling coverings. They have proven to be a contributing factor in how quickly a fire spreads. To minimize the impact interior finish has on fire spread, Chapter 10 of the 2021 edition NFPA 101, Life Safety Code®, establishes basic requirements for interior wall, ceiling, and floor finishes. Chapter 10 outlines two testing options: 1) testing in accordance with NFPA 286, Standard Methods of Fire Tests for Evaluating Contribution of Wall and Ceiling Interior Finish to Room Fire Growth; or 2) testing in accordance with ASTM E84 or UL 723.  Paragraph 10.2.3.1.2 of the 2021 edition of NFPA 101, outlines acceptance criteria for materials tested in accordance with NFPA 286. The acceptance criteria includes: limitations on the spread of flames; peak heat release rate less than 800 kW; and for new installations the total smoke released throughout the test cannot exceed 1000 m2. Any material that meets the criteria outlined in 10.2.3.1.2 can be used wherever a Class A material is permitted. The alternative test method (ASTM E84 or UL 723) results in the material being grouped into a class. There are three classes- Class A, Class B, and Class C which are determined by a material’s flame spread index and smoke developed index. Class A materials will have the lowest flame spread index of the three classifications. The smoke developed index is the same range for all three classifications. For newly installed materials both the flame spread index and smoke developed index is considered, whereas for existing materials only flame spread index is considered. Occupancy chapters may further regulate interior finish beyond what is contained in Chapter 10. In both fires, acoustic material is believed to have been a major contributing factor in the rapid spread of fire. Assembly occupancies do further regulate interior finish. The requirements are the same for new and existing assembly occupancies. In general assembly areas with an occupant load of 300 or fewer, ceiling and wall materials must be Class A, B, or C. In general assembly areas with an occupant load of more than 300, and in corridors, and lobbies, interior wall and ceiling finishes must be Class A or B. In enclosed stairs interior finish materials must be Class A.One other contributing factor was the availability of exits. In both the fire in Thailand and at The Station nightclub, one of the doors to the outside was blocked for use by occupants to allow the band performing to have their own separate entrance/exit. One of the fundamental components of the Life Safety Code is the concept of free egress. Prohibiting people from entering the building via a door is one thing, but not allowing occupants to exit the building via the nearest door is unacceptable. Additionally, NFPA 101 prohibits the means of egress for assembly occupancies from going through hazardous areas such as kitchens, storerooms, closets, stages, and platforms. There are also requirements related to the size of a main entrance/exit, where one exists. History has shown that occupants tend to go out the way they came, even if there is an exit closer. The main entrance/exit provisions are intended to prevent crowd crush situations. In existing assembly occupancies, the main entrance/exit needs to be sized to accommodate at least one-half the total occupant load. For new assembly occupancies that are dance halls, discotheques, nightclubs, or that have festival seating, the main entrance/exits must be wide enough to accommodate two-thirds of the total occupant load. The main entrance/exit for all other new assembly occupancies must be sized to accommodate one-half the total occupant load. If the assembly occupancy is more than one level, then each level must have access to the main entrance/exit and that access must be sized to handle two-thirds (for new assembly occupancies) or one-half (for existing) of the occupant load of that level. The main entrance/exit requirements for certain types of new assembly occupancies was increased from one-half to two-thirds the total occupant load due to a crowd crush event during The Station nightclub fire.Another way the Life Safety Code strives to reduce the risk of crowd crush is by requiring trained crowd managers. All assembly occupancies, with the exception of certain ones used exclusively for religious worship, are required to have at least one trained crowd manager. Depending on the total occupant load, additional crowd managers may be required. Typically, there should be one crowd manager for every 250 occupants. Prior to the 2006 Edition, crowd managers were only required for assembly occupancies with occupant loads of more than 1000. After The Station nightclub fire, the Life Safety Code was changed to require at least one crowd manager for all assembly occupancies. Within 2 minutes of the fire starting at The Station nightclub, there was crowd crush at the main entrance/exit. This led to the main entrance/exit being almost completely impassable. The crowd manager’s responsibilities include understanding crowd management, understanding methods of evacuation, being familiar with the facility evacuation plan, being familiar with the emergency response procedures, and understanding procedures for reporting emergencies.While the cause of the recent fire at the Thai nightclub is still under investigation, The Station nightclub fire was caused by pyrotechnics. To reduce the risk of open flames or pyrotechnics starting a fire in an assembly occupancy they are prohibited unless certain conditions are met. In order for pyrotechnics to be used on stage before proximate audiences, precautions to prevent ignition of any combustible material, satisfactory to the authority having jurisdiction must be met and the use of the pyrotechnic device must comply with NFPA 1126, Standard for the Use of Pyrotechnics Before a Proximate Audience.As we have seen countless times, fires in assembly occupancies, and in particular nightclubs, can result in a high number of fatalities. By carefully considering the use of open flames and pyrotechnics we can eliminate potential ignition sources in these types of occupancies. Additionally, ensuring the interior finish requirements for assembly occupancies are met can help slow the spread of fire. Fires in an assembly occupancy have the added risk of leading to a crowd crush event. Compliance with the means of egress and crowd manager requirements will help reduce the risk of crowd crush events during emergency situations. 
 •  0 comments  •  flag
Share on Twitter
Published on September 15, 2022 17:00

September 12, 2022

Amazon Solar Shutdown Provides Opportunity for Praise and Reflection on Safe Solar Installations

According to recent reports from CNBC and other major news outlets, Amazon temporarily shut down all solar power generation at their North American facilities last year as they worked to investigate potential fire safety issues with these systems. While the details of what Amazon found in their investigations during the shutdown are unspecified and therefore can’t be expounded upon, knowing that Amazon recognized a compounding problem and made safety paramount by shutting down their solar generation at 47 North American sites should be commended. Although there was significant financial loss to Amazon by moving forward with the shutdown and launching the investigation, making the decision to do so aligned with the principles established by the NFPA Fire & Life Safety Ecosystem™—specifically, the company chose to make an Investment in Safety.The NFPA Fire & Life Safety Ecosystem is a framework that identifies the components that must work together to minimize risk and help prevent loss, injuries, and death from fire, electrical, and other hazards. There are eight key components in the Fire & Life Safety Ecosystem. These components are interdependent. When they work together, the Ecosystem protects everyone. If any component is missing or broken, the Ecosystem can collapse, often resulting in tragedy. Almost always we can trace the cause of fire and life safety tragedies back to the breakdown of one or more components. Aside from the aforementioned Investment in Safety, there are several other key areas of the Ecosystem that apply to safe solar installations.Codes, compliance, and skilled workersWith a technology that is constantly changing like solar photovoltaic (PV) power, using the most current codes is critical for a safe installation. Within the Ecosystem, this would fall under the Development and Use of Current Codes component. As an example, NFPA 70,® National Electrical Code® (NEC®), covers the installation of PV systems in Article 690, including the array circuit(s), inverter(s), and controller(s) for such systems. Article 691 covers large-scale PV electric supply stations not under exclusive utility control, such as privately owned solar farms.Yet many areas of the country do not use the most current edition of the NEC, with some areas using editions dating back as far as 2008. That is a 15-year difference between the most current NEC and some of the oldest versions being used. As can be expected, there have been significant changes in product development and safe solar installation requirements over those years. For instance, rapid shutdown is a means of solar equipment reducing the potential for electric shock within 30 seconds of activation of shutdown, intended to raise the level of safety for firefighters that are responding to potential solar array fires. Rapid shutdown was introduced in the 2014 cycle of the NEC so anyone utilizing prior editions would not be providing this level of safety for first responders. This is a clear example of why it is so important to utilize the most current codes for solar installations in order to achieve maximum safety.  Fortunately, even for jurisdictions that are lagging behind in the use of the most recent codes, professionals can choose to take trainings on more recent editions. The NFPA 70, National Electrical Code (NEC) (2020) Online Training Series, for example, provides trainees with key information and interactive exercises on the 2020 edition of the NEC. Another area of the Ecosystem that is necessary for a safe solar installations is Code Compliance. The only way to truly ensure a safe installation is by verifying it through effective code enforcement. Those tasked with inspecting solar installations for safety must consider everything involved while reviewing the systems. NEC requirements as well as manufacturer installation requirements are critical items that must be met. It is also important to remember that code compliance does not end with the initial installation of the system. Any time a solar installation gets updated or modified, it is just as important to have that system reviewed again for continued compliance with the necessary codes as it was to have it inspected in the first place.The individuals that perform the solar installation matter as well. The Ecosystem requires a Skilled Workforce in order to ensure safe installations. Those that are considered skilled are aware of the most current codes and know how to apply them to the installation. They have been trained to properly handle, install, and maintain the equipment that is involved. From an enforcement standpoint, the NEC takes skill a step further by requiring that only qualified persons perform the installation of solar equipment, associated wiring, and interconnections. By definition within the NEC, a qualified person has skills and knowledge related to the construction and operation of the electrical equipment and installations and has received safety training to recognize and avoid the hazards involved. One critical way a Skilled Workforce can be created is through training programs like the ones offered by NFPA. The Photovoltaic and Energy Storage Systems Online Training Series, for example, is a four-part online program that covers topics that can assist with design, installation, maintenance, and inspection requirements for PV and energy storage systems. The training educates users on relevant code requirements for PV systems and ESS not just within the NEC, but also within other leading codes including NFPA 1, Fire Code, NFPA 855, Standard for the Installation of Stationary Energy Storage Systems, NFPA 5000®, Building Construction and Safety Code®, and others. When it comes to safe installations of solar power it is critical that we play offense, instead of defense. Choosing to be proactive by ensuring safe installations that align with the NFPA Fire & Life Safety Ecosystem up front will prevent the need for reactive decisions to correct any potential problems down the line. In the United States alone, solar power capacity has grown from approximately 0.34 gigawatts in 2008 to an estimated 97.2 gigawatts today. With no slowing down in sight, it is critical that those involved in performing solar installations and maintenance are doing so with safety as an important and necessary part of the process. Learn more about all of NFPA’s resources on PV and energy storage systems at nfpa.org/ess.
 •  0 comments  •  flag
Share on Twitter
Published on September 12, 2022 17:00

First draft of NFPA 1970 proposes changes to firefighter PPE standard and will be open for review and Public Comment through January 4, 2023

In my continuing effort to keep interested parties apprised of the latest standards activity related to firefighting gear and conversations about the presence of PFOAs, the first draft of the upcoming edition of NFPA 1970, Standard on Protective Ensembles for Structural and Proximity Firefighting, Work Apparel and Open-Circuit Self-Contained Breathing Apparatus (SCBA) for Emergency Services, and Personal Alert Safety Systems (PASS) has been posted online and is now available for review and Public Comment through January 4, 2023.One of the proposed changes within the draft includes the elimination of the light degradation resistance test on the moisture barrier layer of jackets. It will be replaced by a multi-environmental conditioning procedure (9.1.22) that will be applied to composite test samples before certain tests. Some of the additional changes in the NFPA 1971 portion (protective ensembles) of NFPA 1970 include: Added new requirements for manufacturer indication of “PFAS FREE” gear. (6.1.7.6 & 6.4.13) Added new requirements for acceptable levels of specific restricted substances and added a test method to determine the presence and quantity of specific restricted substances. (7.1.14, 7.4.9, 7.7.6, 7.10.10, 7.13.7, 8.20, & 9.83) The Correlating Committee recommended to consider adding similar requirements for SCBA in Chapter 17 of NFPA 1970 (NFPA 1981 portion). Added requirements to test for ease of cleaning. (8.1.29, 8.4.17, 8.7.26, 8.10.19, 8.13.12, & 9.81) Added requirements to test for effectiveness of cleaning. (8.2.7 & 9.82) Added requirements to test for liquid repellency and penetration resistance of persistent contaminants. (8.2.8 & 9.84) Added requirements to test for leaching of material substances. (8.2.9 & 9.85)It’s important to note that these proposed changes and additions reflect the recommendations of the Technical and Correlating Committee on Hazardous Substances in the NFPA 1970 First Draft Report.As I outlined in a previous blog, NFPA does not create or dictate the provisions within our codes and standards. NFPA is the neutral facilitator of the standards development process; each standard is developed by balanced voluntary technical committees. It is an open and transparent process in which anyone (except NFPA staff) can review and provide input and comment. I strongly encourage everyone who has opinions, perspectives, and insights on these proposed changes to make sure their voices are heard by the committee. Comments will be accepted through January 4, 2023. Anyone who believes the first draft of the standard should be changed to address these and other topics is strongly encouraged to submit proposed changes (public comment) to the next edition of the standard. You do not have to be an NFPA member or on an NFPA Technical Committee to provide comment and propose additional changes.  Anyone (except NFPA staff) can propose a change to the standard by suggesting specific wording and providing a technical rationale through our online submission system, which is accessible at nfpa.org/1970next. The deadline for Public Comment is January 4, 2023.In the following months, the Technical and Correlating Committees will consider all of the proposed changes received by the deadline and will develop a Second Draft of NFPA 1970.  NFPA anticipates that the Second Draft Reports will be posted for public review in the Fall of 2023. Throughout the process, the latest information on this standard can be found at nfpa.org/1970next.
 •  0 comments  •  flag
Share on Twitter
Published on September 12, 2022 17:00

September 11, 2022

A Better Understanding of NFPA 70E: Setting Up an Electrical Safety Program (Part 6 - Inspections)

NFPA 70E®, Standard for Electrical Safety in the Workplace® has requirements for what should be included in an electrical safety program (ESP) but does not provide details. The requirement in Section 110.5(B) to inspect electrical equipment is one where it is the employer’s responsibility to fill in the gaps. A properly documented ESP does not exist until that has been accomplished. The policies and procedures in your ESP are what employees must be trained to follow.The ESP must address the inspection of newly installed or modified equipment. Does your ESP have a way to assign this responsibility? A newly hired, residential electrician may not be the appropriate inspector for a smelting facility. The local electrical inspector often does not inspect equipment that falls under NFPA 70E. Equipment is installed, maintained, repaired, and replaced by an employee or an outside contractor. The responsible person will need to not only determine that an installation meets the applicable manufacturer requirements but also those of applicable standards. This is not limited to electrical standards since things like improperly installed pressure systems in electrical equipment may affect safety. What are the ESP policies and procedures for these inspections? An ESP that requires that equipment be verified as complying with the NEC is not enough. Electrical system and equipment compliance with the NEC is often only determined during building construction. The NEC does not address maintenance nor is internal electrical circuits part of the NEC. However, technicians maintaining motor control equipment must know the applicable NEC requirements. A contracted HVAC technician may be required to provide documentation that their work complies with applicable standards and codes, as well as the facilities requirements. Is their work inspected by a facility employee? Who is authorized to inspect repairs on custom production line equipment? It might not be desirable for the employee performing the work to also perform the inspection. The ESP must address not only these issues but also the training of the employee conducting inspections. The ESP might permit some types of electrical work to be completed without additional inspection. Do employees know which specific equipment is permitted to be energized before or without the additional inspection? A contractor may not follow the same safety protocol. Perhaps, it is not the equipment but the task that directs an inspection before energization. The ESP must address how to document all of this and what is to happen with the results. A requirement for the inspector to evaluate alternate installation methods may provide a means to mitigate hazards or repeated exposures. However, this most likely will not happen without a statement to do so in the ESP.  Proper installation, repair, and modification of electrical equipment play a major role in protecting every employee from electrical hazards. Inspection to determine that fact is a requirement in NFPA 70E. NFPA 70E is a safe work practice standard that is not appropriate to be used as the procedure for equipment inspection. It is critical to train an employee on inspection policies and procedures contained in the documented ESP.
 •  0 comments  •  flag
Share on Twitter
Published on September 11, 2022 17:00

September 8, 2022

Weekly or Monthly No Flow (Churn) Tests of Fire Pumps

Fire pumps are an essential part of many water-based fire protection systems. They are used to increase the pressure (measured in psi or bar) of a water source when that source pressure is not adequate for the system it’s supplying. The right design, installation, and acceptance testing of these pumps will ensure that they are ready and available to protect the building on the day of the acceptance test. After that, once “the keys” are handed over to the building owner, there is no guarantee that the pump will remain in a ready state to work as designed unless it undergoes routine inspection, testing, and maintenance (ITM). The requirements for ITM of fire pumps are found in NFPA 25, Standard for the Inspection, Testing, and Maintenance of Water-Based Fire Protection Systems.&nbspWhile there is a good deal that goes into a robust ITM program for fire pumps, this blog will focus on the no-flow test of fire pumps which is often referred to as a churn test. See this blog for weekly fire pump inspections.What is the purpose of the no-flow test?NFPA LiNK where hot spots can be chosen to find more information about certain inspection and testing requirements for different components.How often is a no-flow test required?The no-flow (churn) test of fire pumps must be conducted at either a weekly or monthly basis. The frequency varies by the type of fire pump; diesel and electric; and both have allowances to extend the time between tests based on approved risk analysis. Generally, diesel fire pumps must be no-flow (churn) tested on a weekly basis.The requirements for electric fire pumps vary. Most electric fire pumps can be no-flow (churn) tested at a monthly frequency. Electric fire pumps which (1) serve fire protection systems in buildings that are beyond the pumping capacity of the fire department, (2) have limited service controllers, (3) are vertical turbine fire pumps, or (4) those taking suction from ground level tanks or a water source that does not provide sufficient pressure to be of material value without the pump all require no-flow (churn) tests at a weekly frequency unless they are provided with a redundant fire pump.StartingThe no-flow (churn) test needs to be conducted by starting the pump automatically. The pump must be started by drawing water from the sensing line to simulate a pressure drop in the system rather than using the “start” button on the front panel of the fire pump controller. An allowance is included in NFPA 25 for an automatic timer using either a solenoid valve drain on the pressure control line for a pressure-actuated controller or another means for a non-pressure-actuated controllers.Run timeElectric pumps must be run for a minimum of 10 minutes while diesel pumps must be run for a minimum of 30 minutes. Personnel Qualified personnel must be in attendance whenever the pump is in operation unless automated inspection and testing is performed in accordance with the requirements of NFPA 25. Check out this blog for more on automated and remote inspection and testing. Qualified personnel is defined in NFPA 25 as competent and capable individual(s) having met the requirements and training for a given field acceptable to the AHJ. Relief valvesNFPA 25 allows the circulation relief valve to open to flow water as a cooling measure. Allowing any additional water flow to prevent overheating is not a requirement of the standard. Flow from the circulation relief valve should be sufficient to prevent over-heating of the pump. It should be confirmed that the circulation relief valve is discharging a small flow of water during the no-flow (churn) test. There are additional details around circulation relief valves and main pressure relief valves in NFPA 25 which personnel should familiarize themselves with.Visual observations while pump is not runningThe following visual observations need to be conducted while the pump is not running. Record the system suction and discharge pressure gauge readings. For pumps that use electronic pressure sensors to control the fire pump operation, record the highest and lowest pressure shown on the fire pump controller event log where such information is available without having to open and energized motor-driven fire pump controller. If the highest or lowest pressure is outside of the expected range, record all information from the event log that helps identify the abnormality.Visual observations or adjustments while pump is runningThe following visual observations or adjustments need to be conducted while the pump is running. Pump system procedure as follows: Record the pump starting pressure from the pressure switch or pressure transducer Record the system suction and discharge pressure gauge readings Adjust gland nuts if necessary Inspect the pump packing glands for slight discharge Inspect for unusual noise or vibration Inspect packing boxes, bearings, or pump casing for overheating Record pressure switch or pressure transducer reading and compare to the pump discharge gauge For pumps that use electronic pressure sensors to control the fire pump operation, record the current pressure and the highest and the lowest pressure shown on the fire pump controller event log. For electric motor and radiator cooled diesel pumps, check the circulation relief valve for operation to discharge water Electrical system procedure as follows: Observe the time for motor to accelerate to full speed Record the time controller is on first step (for reduced voltage or reduced current starting) Record the time pump runs after starting (for automatic stop controllers) Diesel Engine system procedure as follows: Observe the time for engine to crank Observe the time for engine to reach running speed Observe the engine oil pressure gauge, speed indicator, water, and oil temperature indicators periodically while engine is running Record any abnormalities Inspect the heat exchanger for cooling waterflow Steam system procedure as follows: Record the steam pressure gauge reading Observe the time for turbine to reach running speed In addition to the above, the discharge temperature of the water must be monitored, and the pump shut down if necessary to prevent exposing the pump and/or driver to excessive temperatures. Where the recorded pressure readings on the discharge and suctions gauges show a difference that is greater than 95 percent of the rated pump pressure, the situation needs to be investigated and corrected.The weekly or monthly no-flow (churn) test is an important part of ensuring that a fire pump can be continually relied upon in the event of a fire. These tests will help to ensure that the pump will start and will not overheat in the event of a fire. At an annual frequency, flow testing will be performed to further verify the complete operating condition of the pump. NFPA has a number of resources related to fire pumps and the ITM required for them. Some of these include NFPA 20 Online Training Series, NFPA 25 Online Training Series, the NFPA 25 Handbook, the Certified Water-Based Systems Professional (CWBSP) credential, and the Certified Water-Based Systems Professional Learning Path among many others.
 •  0 comments  •  flag
Share on Twitter
Published on September 08, 2022 17:00

National Fire Protection Association (NFPA)'s Blog

National Fire Protection Association (NFPA)
National Fire Protection Association (NFPA) isn't a Goodreads Author (yet), but they do have a blog, so here are some recent posts imported from their feed.
Follow National Fire Protection Association (NFPA)'s blog with rss.